Voltage Drop
Voltage drop is the decrease in electric potential along a current-carrying path because that path has electrical resistance. Cable length, current and the conductor resistance per metre determine the estimate in this tool.
Essential relationship
\Delta V=I\,R_{\mathrm{per\ metre}}\,L_{\mathrm{full\ path}}Essential relationship
The circuit quantities BB Calculator asks for
Current [A] Non-negative current through the full circuit.
Effective full-circuit resistance per metre [Ω/m] Choose the resistance per metre consistent with the full route.
Total full-circuit path length [m] Defaults to 1 m; include the return path where applicable.
Follow the current through the cable
Open Drop, enter Current and effective Ω/m, then supply the total current-path metres. A DC two-wire example with 10 m outward and 10 m return uses 20 m here. Select Calculate after checking that r and L describe the same whole loop.
Reported voltage loss
Primary: Voltage drop (V). Supporting details show Effective full-circuit length (m) and Resistance per full-circuit metre (Ω/m). Current and r may be zero; length must be positive. The result includes a circuit-path and electrical-code caveat.
A complete wire route
For 10 A, r = 0.02 Ω/m and L = 20 m, ΔV = 4 V. Using only the outward 10 m with the same per-metre assumption would understate the complete loop. Match resistance and path definitions before multiplication.
For 10 A, r = 0.02 Ω/m and L = 20 m, ΔV = 4 V. Using only the outward 10 m with the same per-metre assumption would understate the complete loop. Match resistance and path definitions before multiplication.
Using the result responsibly
Voltage drop is one part of an electrical installation assessment. Cable ampacity, temperature, AC reactance, protection and local code requirements require separate consideration; the app provides an ohmic estimate.
Voltage drop is one part of an electrical installation assessment. Cable ampacity, temperature, AC reactance, protection and local code requirements require separate consideration; the app provides an ohmic estimate.
What should the diagram convey?
The first figure distinguishes the outbound and return wires; the second isolates length sensitivity; the third performs the complete numerical substitution.
The first figure distinguishes the outbound and return wires; the second isolates length sensitivity; the third performs the complete numerical substitution.
Quick answers
Why include the return conductor?
A two-wire DC circuit carries current through both the outbound and return paths; enter the total applicable path length.
What does Ω/m mean?
Ohms per metre describes the effective resistance associated with one metre of the specified circuit path.
Can zero current be entered?
Yes. With zero current the calculated voltage drop is zero.