Three-phase Power

Use this calculator

A balanced three-phase electrical system uses three AC phases displaced by 120°. Line-to-line RMS voltage and line current, together with power factor, determine its apparent, real and reactive-power magnitudes.

Balanced three-phase power at line values

S = \sqrt{3}\, V_{L}I_{L}
P = S\, PF

S = apparent power in VA; P = real power in W; Vₗ = line-to-line RMS voltage; Iₗ = line current; PF ∈ [0,1]. Reactive magnitude is Q = S√(1−PF²).

The power quantities relate geometrically. Apparent power describes voltage–current capacity, real power represents energy transfer per unit time and reactive magnitude completes the right-triangle relationship S²=P²+Q².

Enter the system’s line measurements

3-phase: Line voltage, Line current, Power factor.

In 3-phase enter Line voltage, Line current and Power factor. Example: 400 V, 10 A and PF=0.8 give S≈6.928 kVA, P≈5.543 kW and reactive magnitude≈4.157 kVAr.

Read kW, kVA and reactive magnitude

Real power is displayed first in kW, then Apparent power (kVA) and Reactive power magnitude (kVAr). The tool requires non-negative line magnitudes, PF from 0 to 1 and finite results; it explicitly assumes a balanced system.

Why √3 appears

For a balanced three-phase system, combining three phase contributions with line rather than phase measurements yields √3 in the line-voltage/current formula.

Balanced sinusoidal phase voltages are separated by 120° in electrical phase.

For a balanced three-phase system, combining three phase contributions with line rather than phase measurements yields √3 in the line-voltage/current formula.

What happens when PF changes

For fixed line voltage and current, apparent power remains the same; real power scales with PF, while reactive magnitude decreases as PF approaches 1.

A balanced three-phase estimate combines line RMS voltage, line current and power factor.

For fixed line voltage and current, apparent power remains the same; real power scales with PF, while reactive magnitude decreases as PF approaches 1.

Interpreting reactive output

The program reports magnitude only. Phase-leading versus phase-lagging direction requires additional circuit information beyond its input fields.

For 400 V line RMS and 10 A, PF = 0.8 yields approximately 5.543 kW real power.

The program reports magnitude only. Phase-leading versus phase-lagging direction requires additional circuit information beyond its input fields.

Interpreting the three result units

For balanced 400 V line-to-line RMS, 10 A line current and PF=0.8, apparent power is about 6.928 kVA, real power about 5.543 kW and reactive magnitude about 4.157 kVAr. Their magnitudes satisfy S²=P²+Q² using consistent unit scales.

Quick answers

Which voltage should I enter?

Line-to-line RMS voltage as stated in the field and result assumptions.

What does kVAr mean?

Kilovolt-amperes reactive, a unit of reactive-power magnitude.

Can PF exceed 1?

No; the calculator accepts power factor from 0 to 1.